Stabilizer Model: STAB3
Following checks and corrections are applied during Validation and AutoCorrection.
- If 0 < Tx1 < Mult*TimeStep then Tx1 = Mult*TimeStep
- If 0 < Tx2 < Mult*TimeStep then Tx2 = Mult*TimeStep
- If 0.0 < Tt < 0.5*Mult*TimeStep then Tt = 0, ElseIf 0.5*Mult*TimeStep < Tt < Mult*TimeStep then Tt = Mult*TimeStep
- If Kx = 0 then Kx = Mult*TimeStep
- If VLim < 0 then VLim change sign to positive.
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Model Equations and/or Block Diagrams
Parameters:
| Tt | Time constant, sec |
| Tx1 | Time constant, sec |
| Tx2 | Time constant, sec |
| Kx | Gain |
| Vlim | Limit |